ElectraSeal® ESD Concrete
Sealer-CSI Product Guide Specification
|
|
This product guide specification is
written in accordance with the CSI MasterFormat,
SectionFormat, and PageFormat standards. It simplifies
the process of specifying a permanent, metal-free,
low-VOC anti-static concrete treatment under Section 03
35 00 (Concrete Finishing) or Section 09 61 13 (Flooring
Treatment).
To request this specification document as an editable
Microsoft Word document (.docx) for direct integration
into your project master manual, please contact our
engineering support team directly via email (techsupport@unitedscp.com)
or by telephone at 719 676 3928 (option 2)..
The section must be
carefully reviewed and edited by the Architect to meet
the requirements of the project and local building
codes. Coordinate this section with other
specification sections and the drawings.
Specifier Note:
Please delete these text boxes before publishing your
project manual. |
SECTION 09 61 13
STATIC-CONTROL CONCRETE SEALER
PART 1: GENERAL
1.1 SECTION INCLUDES
A. Fluid-applied
hygroscopic, static-dissipative polymer concrete sealer system for
interior concrete substrates.
B. Electrical grounding
hardware and foil installation instructions.
1.2 RELATED
REQUIREMENTS
A.
Coordinate with Section 03 30 00 (Cast-In-Place Concrete), Section
03 35 43 (Polished Concrete Finishing), and Section 01 33 00
(Submittal Procedures).
B. Section 03 35 43 -
Polished Concrete Finishing.
1.3 REFERENCES
A. ANSI/ESD S20.20-2021
- Protection of Electrical and Electronic Parts, Assemblies, and
Equipment.
B. ANSI/ESD STM7.1 -
Floor Materials - Characterization of Resistance.
C. ESD/STM 97.1 - Floor
Materials and Footwear - Resistance Measurement in Combination with
a Person.
D. ASTM F1869 - Standard
Test Method for Measuring Moisture Vapor Emission Rate of Concrete
Substrate Using Anhydrous Calcium Chloride.
E. CDHP (California
Department of Public Health) Standard Method V1.2 - Emission testing
for volatile organic compounds.
1.4 ADMINISTRATIVE
REQUIREMENTS
A. Pre-Installation
Meeting: Convene a mandatory pre-application meeting [__] weeks
prior to starting installation.
Attendance: Contractor,
Applicator, Architect, and Owner's Representative.
Review: Substrate preparation, moisture testing, grounding
placement, application sequence, and curing protections.
1.5 SUBMITTALS
A. Product Data: Submit
manufacturer's technical data sheets, electrical properties, and
installation guidelines.
B. Sustainable Design
Submittals: Submit documentation verifying low-VOC compliance
to CDHP V1.2
1.6 QUALITY ASSURANCE
A. Quality Assurance:
Submit documentation verifying applicator has a minimum of five (5)
years of experience with similar fluid-applied industrial coatings
or has been pre-approved by the manufacturer of the product (United
Static Control Products).
1.7 DELIVERY,
STORAGE, AND HANDLING
A. Deliver materials to
the site in the manufacturer's original, unopened containers with
intact labels showing product name, batch number, and SDS sheets.
B. Maintain storage and
installation temperatures between 60 degrees F and 90 degrees F
within a fully enclosed, weather-tight facility.
Left off here - see E Seal 6 email
PART 2: PRODUCTS
2.1 MANUFACTURERS
A. United Static Control
Products Incorporated, 2124 S. Prairie Ave, Building D, Pueblo, CO
81005. Phone: (719) 676-3928.
2.2 MATERIALS
-
Static Dissipative Sealer:
ElectraSeal® ESD Concrete Sealer:
-
Formulation: Metal-free, low-odor,
hygroscopic polymer chain formulation.
-
VOC Content: Less than 55 g/L. Meets
CDHP V1.2
-
Environmental Restrictions: Do not
install in spaces with a sustained relative humidity below 30%.
-
Composition Safety: 100% Free of
Dibutyl Phthalates and Formaldehydes.
B. Grounding Components: Manufacturer-supplied
aluminum or copper foil grounding foil strips or approved
alternative grounded metal equipment racks.
PART 3: EXECUTION
3.1 EXAMINATION AND PRE-TESTING
A. Substrate Verification: Verify concrete
substrate is clean, visibly dry, and free of bond-inhibiting
contaminants (wax, oil, grease, or incompatible curing
compounds).
B. Moisture Testing: Conduct concrete vapor
emission testing per ASTM F1869. Specifier Note: ElectraSeal
features a microporous structure capable of handling high vapor
emissions, but anomalies over 8 lbs/1,000 SF/24 hrs should be
evaluated by the manufacturer before proceeding.
C. Bond Pre-Test: Perform a localized bond and compatibility
pre-test if applying over existing densified, sealed, or
diamond-polished concrete surfaces.
3.2 APPLICATION
A. Grounding: Install manufacturer-provided
aluminum ground foil strips in accordance with grounding
documentation, or verify placement of permanently grounded steel
structures (such as server racks) acting as alternate grounding
paths.
B. Application Method: Apply product using a clean microfiber
mop, high-speed finish applicator, or automated spray equipment.
C. Coverage Rate: Apply uniformly at a coverage rate of
approximately 1,500 square feet per gallon per coat.
D. Coating Sequence: Apply a minimum of three (3) full coats,
allowing adequate drying time between subsequent coats according
to manufacturer instructions.
3.3 COMPLIANCE TESTING & CLEANING
A. Testing: Prior to final handover
and building occupancy, test the cured floor for compliance with
ANSI/ESD S20.20-2021 compliance verification standards.
B. Post-Installation Maintenance: Initial cleanup
and maintenance must strictly utilize approved neutral cleaners
(such as ElectraClean) and burnishing compounds (such as
ElectraShine) to avoid degrading ESD characteristics.
3.4 PROTECTION
A. The ElectraSeal system gains maximum hardness and
durability
during a curing phase lasting approximately 2 weeks. Protect
floor coating system while curing and especially during move in
of heavy equipment.
END OF SECTION
Reviewed for Accuracy -